It's almost tradition to have a rack with UPS's in the bottom and then the rest of the space filled with servers or drive arrays.
We wouldn't ever think of putting a tiny backup generator in the bottom of every rack, so why do we put a battery storage system there? Also, with the advances in battery chemistry technology that improve reliability and density, it's only a matter of time until Lithium chemistry batteries are available and that also increases the risk of fire.
Is there any reason not to move backup power to another room, or even to a separate structure like how they put backup generators on a pad outside of the building?
https://www.cnet.com/news/google-uncloaks-once-secret-server...
See http://apec.dev.itswebs.com/Portals/0/APEC%202017%20Files/Pl... page 6.
https://storage.googleapis.com/pub-tools-public-publication-...
> A data center typically spans four rooms, called suites, where racks of servers are arranged in rows. Up to four MSBs provide power to each suite. In turn, each MSB supplies up to four 1.25 MW Switch Boards (SBs). From each SB, power is fed to the 190 KW Reactive Power Panels (RPPs) stationed at the end of each row of racks.
https://research.fb.com/wp-content/uploads/2016/11/dynamo_fa...
The UPS role is taken more by BBUs (Battery Backup Units). https://www.youtube.com/watch?v=KNsposM0sJE has lots of info about them.
(I work for FB, on entirely unrelated things)
https://datacenterfrontier.com/google-unveils-48-volt-data-c...
Yes: longer cables.
See Figure 1 in the Schneider-APC white paper, where they have "Electrical Space", "Mechanical Space" (HVAC), and IT Space:
* https://download.schneider-electric.com/files?p_File_Name=VA...
Power is generated hundreds of kilometres from where it is used, so having your UPS room a few dozen metres from your actual DC room isn't a big deal. I-squared-R losses aren't going to be that huge.
Europe uses 400Y/230 for nominal low-voltage distribution (see Table 1 in above), so stringing some 400V extra copper to the PDUs, which then have 230V at the plugs, isn't a big deal.
Not all Li-ion chemistries are equal. In particular, the increasingly popular LiFePO4 (LFP) technology has much higher energy density, longer lifespan, improved environmental characteristics, and similar if not better safety characteristics compared to lead-acid.
(Besides sharing lead-acid's very low risk of fire, LiFePO4 also contains no corrosive acids which could damage and short equipment if a leak were to occur.)
Isn't lead-acid prone to releasing hydrogen gas?
When jump-starting a car, it is commonly recommended to connect the ground (black) cable to the chassis, not to the battery's black terminal, to avoid a spark igniting the hydrogen and causing an explosion.
VRLAs can overcharge and catch fire just like flooded batteries. They just don't go kaboom as much or spray acid everywhere. When having thousands of batteries in a room, one of them catching fire is inevitable. This is why batteries are in separate fire containment rooms, on nonflammable shelving, in redundant strings, and protected by FM200.
I've seen people use UPSes to allow them to rearrange wiring. I've seen them fail by relying on the UPSes as well, of course.
If you wire the entire room with 2-3 separate electrical systems all powered off of separate remote UPSes, you can do whatever you want, but it's harder to change your mind or build out incrementally if you do.
Battery rooms were traditionally separate, used lead acid batteries, were surrounded by thicker walls, and equipped with FM200, just like main datacenter floors. They were typically placed near the transfer and PDU switchgear. I wouldn't put anything more flammable than LiFePO4 in a battery room, much less anywhere near a server.
It's people who decide to throw away conventions, common sense, and building codes because "they know better" who get into trouble.
I suspect this datacenter company could be sued into oblivion.
All racks and servers were connected to dual power feeds, so even when one of the feeds goes down the servers should run fine.