by windexh8er · 3y ago · 0 comments
I live in a northern, Midwestern state and our coop (part of MISO) offered a one time $1500 and continued discounts (11%) per month on electricity for the capability to control utility curtailment (power control to the unit, no ability to adjust set-point or collect any other data). For winter it can only be in buildings that are non-primary living and can only shut off power to an electrical heating appliance (heat pump, boiler, etc). In the summer they can curtail your heat pump / AC for up to 15 minutes at a time.
I see the curtailment notification on my thermostat on hot days. But the house never gets warm. I have a newer heat pump that is rated up to 22 SEER2 and compared to my old on/off AC unit the variable speed unit makes a huge difference in performance, cost and noise levels. I never hear it running when it is and so during curtailment I don't notice it unless I see the notification.
And I believe the contract states curtailment events can only happen up to 4 times in a given day and cannot happen more than once an hour.
I do find it interesting that these terms are still valuable to a power company. Obviously being able to shed the load for 15 minutes is fantastic, but I would think the system would then just use more energy (say for the next 45 minutes) to make up for it. But perhaps staggering the curtailment times, and paying the debt of more draw from the units that were curtailed by doing even more curtailments, can kick the can down the road enough for the few hours they need to smooth peak load?
Also just a guess: is the story with heating that your heat pump is sized based on your max heating load, and so losing up to 25% of its capacity on the coldest days means it would never be able to catch up?
The unit I have has a HSPF2 rating of 10.5. It's very efficient at the transfer of the heat available. Heat pumps can extract more energy than the consume. New heat pumps can operate over 300% efficiency. The best furnaces are generally in the mid-90 percentages.
I have a dual-fuel system and can set where the heat pump locks out. The system is rated to a COP of 1.75 at 5F. Meaning it's still over 100% efficient at that temperature. The unit will operate down to -22F but would be at, likely, less than 50% capacity of output. To save on wear and tear of the unit, however I have my setpoint lockout at 15.
It would have to be significantly below 0 for days on end to have a problem. But even then the furnace would be providing primary heat. There are people in my area that heat their entire home with ductless heat pumps [0]. My unit is rated at 48k BTU. The furnace at 100k BTU. I only really "need" the furnace for emergency. But we do have sub-zero highs rather often and during those days the heat pump would be running continuously.
I also have an 80 gallon hybrid heat pump water heater which has saved us thousands over the last few years. 98% of the year it only uses the heat pump.
[0] https://www.energyvanguard.com/blog/can-a-heat-pump-work-in-...
Can I ask why you got a heat pump with such a high SEER rating? I look at flyers advertising heat pumps near me and the price differential between 16 SEER and 18/20 SEER units just doesn't seem worth it at all even accounting energy savings.
[0] https://yourallweatherhvac.com/media/2022-Carrier-Cool-Cash-... (PDF) [1] https://techxplore.com/news/2021-07-minnesota-energy-law.htm... [2] https://www.minnpost.com/greater-minnesota/2023/03/dfl-energ...
I got a $1400 rebate from the manufacturer at the time $2000 tax credit from the fed and another $1200 from the state.