First of all, let's assume less than ideal conditions so base our calculations on 115V. 2,500 watts is going to be 21.7 amps; assuming a continuous load (which is pretty reasonable for a whole house) is going to need a breaker and wiring that's rated for 125% of that, or 27.2A.
That means the supply needs to be #10 wiring and should be fitted with a 30A breaker at the disconnect. A temporary power tap is not a suitable disconnect. And I highly doubt it's got 10 gauge wiring.