Of course they would because it's work being taken away from them but it would be allowing people to plug generators into ring finals with unidirectional breakers. It's not even guaranteed that the circuit is protected by anything newer than fuse wire or an MCB. No guaranteed earth leakage detection. No guaranteed surge protection. Relying on the cheapest inverters to sync frequency accurately. And
I have more faith in German standards and work ethic than our own.
https://www.digikey.com/en/articles/anti-islanding-and-smart...
Consider 100 homes on a power line network and the breaker trips. They probably draw 50kW on average, more if it's hot or cold and AC is on. Unless there's enough power generation available to power that entire load, voltage will drop and any halfway reasonable hardware should give up.
question is whether the ones allowed for sale implement it well and are tested for it
So in the UK we have 2.5mm^2 wires in a ring on a 32A MCBs... Of course a 2.5mm^2 wire is rated ~20A so any issues with the ring (sockets still work since connected from the other branch) can burn the wire before the MCB trips...
From what I understand the UK allowed it because of a severe postwar copper shortage and it persists to this day because it's allowed and a bit cheaper.
If you plug it into an overloaded ring final (which is not uncommon in the UK - half our house's sockets are on a single ring), you have to rely on the generator being able to detect faults to protect that circuit.
You could also overload that circuit's wiring. If you have a a 16A Ecoflow, plug it into a 32A ring, you could draw 48A before tripping the grid circuit breaker, potentially causing significant heat in the wires. Dinky 3A generators won't do that but I don't think they're the limit our government are talking about.
What do you mean by "guaranteed surge protection"? Are you an electrician to write like that?
If the circuit will be supplying power too (e.g. battery storage, an EV and EVSE that supports powering the house from the EV, etc) then you need a bidirectional RCBO.
People with no differential fault protection need not worry about any of this, they'll just be killed when it goes badly wrong.
Source: Am a UK electrician
Example: https://assets.cef.co.uk/downloads/pdg/wylex_nhxs1b32_datash...
EDIT: To say nothing of people with unidirectional electricity meters; plugging these into those setups will get them prosecuted for electricity theft. All SMETS 2 smart meters are bidirectional; you'd best check your meter if it isn't one of those.
Pre-smart non-prepayment electronic meters (for those with old meters, still submitting manual readings, and paying by direct debit) will be fine. Most of these meters, and all smart meters, are inherently bidirectional, because they maintain 4 counts (energy imported and energy exported, in kWh and kVARh) and your energy provider will do all the necessary math to figure out what to actually bill you for (residential customers are not billed for kVARh usage).
The UK government in 2011 announced plans to have 50 million smart meters installed by the end of 2020. In typical overpromise underdeliver government fashion, they didn't even achieve half of that; by then, only 23.6 million had been installed, and of those, 4.5 million had stopped working because they were initially (and stupidly) designed to be tied to a specific energy provider and the customer had changed provider. This even affected me.
Nevertheless they'd still accurately track energy consumption and export even if they'd lost their reporting capability, so you have nothing to fear here. This situation has been rectified at the redesign stage with provider-independent SMETS 2 meters, and all SMETS 1 meters still in service have been hotpatched to bring them into line (restoring their smart functionality regardless of provider).
Even today (well, as of last September), this number is only 40 million, with only 36.7 million of them actually working as designed (reporting readings automatically).
This leaves up to 16 million properties with a meter that may stop working and expose you to a theft investigation when you obtain generation capacity that even momentarily exceeds your usage (for example if you have a dual RCD board and one of the RCDs trips, taking out half of the circuits in your home, but not the one the inverter is plugged into).
Realistically the true figure is probably around a quarter of that; prepayment meters were very popular among the renting population of the time, and those who wanted to track their energy usage carefully and only pay for it with cash as and when needed, and sometimes people had these meters forced upon them by suppliers after the customer had demonstrated poor payment history, but they were far from the norm.
Average home owner buying plug-in solar at a supermarket isn't going to know or care about any of this. They'll just plug it in, and it will work, until one day maybe it doesn't and their supplier opens a theft investigation.
However in the case of a UK home, where you may have a single ring circuit connecting all the sockets on the whole floor, what's in the breaker panel isn't going to protect you with plug-in solar anyway. Better hope what you are plugging in meets UK standards and isn't just some Chinese rubbish that claims it does.
The conventional practice in the US is still to use GFCI receptacles rather than breakers.
But that's rather the point here that consumers are the ones who are going to be plugging in these devices, with no appreciation for their circuits and safety devices. The only code that matters is the last version of it adhered to when their home was last wired. In extremes, that can be 40 years or more.
Not to mention that most houses aren't up to current electrical standards, much less fire codes.
It isn't as if electric charge coming from balcony solar panels is some new magical-seeming type of electricity.
Also, why do wires have to be fixed to joists every 300 mm? It's not about the electrons.