EDIT - could you elaborate on how heating the bleed valve is a good way of controlling it? Isn't it moisture based? --Andrew (Terg.is)
at rest: radiator full of air, valve open
steam begins flowing: steam is displacing air from radiator, bleed valve begins heating up
bleed valve closes: radiator is now full of steam, some of which condenses and ideally runs back down pipe, if your building hasn't shifted too much over the years. any condensed steam is replaced with new steam from pipe
boiler stops: steam is no longer coming up the pipe. As the steam in the radiator condenses we suck air back in through the bleed valve. radiator is cooling.
bleed valve opens: at some point the radiator cools enough that the bleed valve opens. We are now ready to begin the cycle again.
Additionally, I think there is a time delay component in the bleed valve to let it get the air good and purged before it closes.
The valves close when steam reaches them, due to a small amount of alcohol in them turning into vapor and exerting mechanical force to close the valve.