Currently system is running 20% methanol to combat the 29degF EWT (entering water temp) in deep winter. House is in Zone 6a.
One thing I learned in researching all of this is that use of ground source over many years can move the bulk ground temp permanently. (House also has water-to-air water furnace for AC). If heat pulled from ground in winter is not sufficiently replaced by heat added during summer, can move bulk ground temp over time. (If densely packed residential ground loops ever became a thing, I think this is a real risk.). But I am not sure if we have this issue at our place, still in first year, not enough data points.