by n4r9 · 1mo ago · 0 comments
Data centers tend to concentrate their water usage within urban areas, causing a strain on local resources. The value of their output is much less tangible. Their water consumption scales up around tenfold if you consider the indirect usage from generating the electricity.
But on the other hand; yes, it would also help enormously if people ate less meat.
By “strain on local resources” are you just stating the fact that they use resources? Or are you trying to imply that it causes problems for those resources?
Companies don’t just buy land, connect to water and power, and then the utilities get caught off guard when the water system is suddenly strained by water going somewhere. There are processes for approving this before connection.
If a new project is causing a “strain on resources” then the utility planners have failed that community.
A recent datacenter proposal near me was going to be built on a ~35 acre site. The entire site projected to use ~300 gallons of water a day when fully operational. That's including toilets, irrigation, etc. A household on a quarter acre lot in that area often uses 10-15,000 gallons of water in a month. 35 acres cut into quarter-acre-ish lots means a bit under 140 households. We'll cut it down and say 100 after streets and what not. That lot being a neighborhood like the others nearby would probably use at least a million gallons of water in a month, about 33,300+ gallons a day.
https://www.brookings.edu/articles/ai-data-centers-and-water...
> You can't build an apartment complex here, because our water/sewer system is already over capacity
/ignores that statement and builds the apartment complex because "omg, we need more housing" arguments are used to not pay attention to consequences
/water and sewer system can't keep up and all kinds of expensive problems occur
Call it an echo chamber but when it comes to data centers that's the preponderance of news that I read. These two stories are about the county next door to mine. The first story highlights how the builders of the data-center continuously broke zoning laws. The second story from a month later describes how the board of commissioners let all that slide and approved construction to continue.
https://www.cpr.org/2026/08/07/weld-county-ai-data-center/ https://www.cpr.org/2026/09/10/weld-county-officials-approve...
But it's not just my state:
https://www.theguardian.com/environment/2026/sep/25/new-jers...
Those guys were fined a "record" $1.1 million, and:
> The state is mandating DataOne apply for and obtain the required permits or cease operations, but is giving the company 45 days to do so, according to a NJDEP spokesperson. During that time, regulators are allowing the facility to continue running the generators.
That fine is a slap in the wrist.
That's way beyond what utility planners can reasonably plan for.
This isn’t some unusual outcome. It’s like one of those maps that purports to show one thing but really just shows population density.
There's no river or creek not used for drinkwater consumption or management, and they are all connected to agricultural use and transportation (canal water levels) as well. It's one big system, and farmers cheating on how much they pump up is already too big of a proboem for this to not matter.
When you apply for a connection to a utility, they make you tell them your potential usage so they can assess if they can even connect you.
> Data centers tend to concentrate their water usage within urban areas
Ahh, what? The world's greatest concentration of data centers is in the suburbs surrounding Washington, D.C., USA. Almost none of that would be classified as urban. I offer a counterpoint: The vast majority of data centers are suburban, rather than rural or urban. > Their water consumption scales up around tenfold if you consider the indirect usage from generating the electricity.
This is bullshit. I already disproved this myth here: https://news.ycombinator.com/item?id=49119054In short, "More than 90% of this is returned to source."
At first you had me, but then I realised it's not true if the price is building more data centres! That was just a trick to make the climate worse! Grr /s
I'm personally willing to change my life to help the planet and nature in general to the point it doesn't affect my wellbeing (as in health and safety). For me, personally, the problem is not changing per se, but people finding no amount of change enough, always moving the goalposts with "but, what if" clauses.
The problem with datacenter water use is the state of the water leaving the data center. Agriculture and meat industry can reuse the water multiple times from cleaner to dirtier processes and return it to the nature with reasonable processing.
The additives used by datacenters in some cases can't be filtered or processed out practically or in economically viable ways, so the water returns back as unusable, esp. if they get water from a body of water and return it with added chemicals the process gets very damaging.
Why would any water be returned? Datacenters (and literally every industrial process that requires cooling) use water for evaporative cooling. The water evaporates, then returns as rain elsewhere.
The only water being "returned" I can think of would be from the intermittent or continuous blowdown systems to maintain TDS levels; but blowdown is a small fraction of the water consumed and is typically returned back via the city sewer system.
We're talking about water that's released in general use, right? I would expect a closed cooling loop to have some biocides but have almost none of that leave the system.
And one datacenter had a weird bacteria that one time.
Concentrated salts and minerals — calcium, magnesium, silica, and other dissolved solids at 3–5× the concentration of incoming makeup water, depending on the cycles of concentration the system operates at
Corrosion and scale inhibitors — chemical additives applied to protect the cooling system's metal components from scale buildup and corrosion; typically phosphate-based or polymer compounds
Biocides — chemical treatments to control Legionella and other biological growth in the cooling tower; commonly chlorine, bromine, or isothiazolone compounds
Heavy metals — leached from piping, heat exchangers, and cooling system components; copper, zinc, and chromium are common depending on metallurgy
Glycols — in some configurations where freeze protection is required
PFAS compounds — some liquid coolants used in immersion and direct liquid cooling systems contain fluorinated compounds; some refrigerants used in air cooling are classified as F-gases (a PFAS subcategory)
https://commercialwaterlab.com/news/data-center-water-use-co...