by terom · 2y ago · 0 comments
That sound dangerous. The larger fuse sized for the 20A socket will not protect the smaller conductors in the cable sized for the 10A plug, they can get overloaded.
The three-phase / industrial CEE plugs and sockets used in the EU are sized for 16A/32A/63A/125A. It's perfectly legal and safe to make a passive adapter that lets you plug a 32A appliance or distribution box into a 16A socket, you just can't load it higher than the 16A fuses on the socket. Going the other way around (16A plug into a 32A socket) you MUST have a circuit breaker in between to provide the required overload protection.
If I have a 3 Watt doohickey, I don't go looking around to find a 0.025A socket, I plug it in to my 15A wall socket and everything works great.
Appliances themselves with their own input fuses and captive cables are less risky, although some kind of internal wiring short could still get all melty.
It's true that sizing the plugs that way does prevent you from plugging a 20A appliance into a 10A extension cord, which makes sense.
The breaker is there to protect the wiring in the building, nothing more. It’s spec’d to the gauge of the cable in the wall typically.
So the ampacity of the connector (duplex and plug) is meant to reject certain combinations (plugging a 30amp appliance into a 15amp duplex/circuit). It's obviously very easy to get around that by just wiring things together wrong (18AWG wire on a 30Amp circuit), but by design, a 30amp appliance with the proper plug cannot be plugged into a 15amp outlet.
Of course, this is informed by the electrical code in my home country, so I understand that other places and people have different experiences, but electrical accidents have been on a steady downward trend since the 80's, so the NFPA NEC has to be doing at least some things right.
Over in my 230V corner of the EU, CEE 7/3 sockets are pretty much the only thing I'm aware of for new wiring, with the unearthed CEE 7/1 sockets still present in older installations. Both are rated for 16A, with either 10A/1.5mm² or 16A/2.5mm² branch circuits from the distribution board. It would be unheard of to wire those up with any higher ampacity at risk of overloading the sockets - although recent experience with e.g. EVs has shown that they're not actually suitable for sustained loads at 16A, given e.g. wear and tear on the sockets.
Unearthed appliances do commonly have CEE 7/16 plugs rated for 2.5A, particularly things like wall warts or USB chargers, which does fit into a CEE 7/3 socket.
I recall seeing CEE 7/16 (2.5A europlug) sockets, although those may have been imports from elsewhere in the EU. I suppose those would have the same issues if wired up to the same distribution circuits. But extension cables for those are rarer, the only ones I've ever seen are CEE 7/7 plug (16A) -> CEE 7/16 sockets (2.5A).
For residential/commercial loads over 16A / 3.2kW, it's all CEE / IEC 60309 connectors, and those are treated like distribution circuits with overload protection sized appropriately for the connectors/cables.
I realize I'm nitty but this is a technical-minded forum after all.
"amp" also seems to be more common to write than "A" for electricians. Remember that the SI standardization of unit abbreviations is actually a pretty modern thing, so lots of fields existed before unit abbreviations were standardized and continue to use existing practices.
Yes though, ampacity is the correct word (for my home country). "Current" is an instantaneous measurement of current flow. That they use the same unit is pretty convenient for planning circuits. https://en.wikipedia.org/wiki/Ampacity#:~:text=Ampacity%20is....