In server areas and extremely specialized stuff? Yea, sure. But we’re talking desktop PCs here.
Many houses run circuits that are rated for 20 amps even if they don't have the right outlet for it so this is an inexpensive upgrade for most.
Most of the US utilizes the NEC for installation compliance. Per NEC, 15A-style outlets are "to code" on 20A circuits unless a single recepticle ("dedicated") circuit — in which case a 20A-style recepticle MUST be installed.
For any electric appliance (including computers) which operates for 3hrs+ ("continuously"), the circuit rating is reduced to 80% capacity (e.g. only 16A load allowed continuously on a "20A circuit" == only 1920W computers allowed on 20A circuit, 1440W on 12A).
Pro tip: check your own PSU, but practically all modern computers can handle AC input 100-240V (all you need is the correct IEC power cord for a 240 US plug).
I have fixed enough melted devices in my career to always twice-torque each&every connection I make. For temporary extension cords/plugs, "twist lock" ends are worth all the extra dollars.
Protips: use Eeez-Ox (a conductive paste which inhibits corrosion) for high-load applications (non-data, only). My own gamerig's AMD GPU has it (sparingly applied) within its dual 8-pin connectors. I supply the 8-pin connectors from a single pair of 8awg copper, which is directly soldered within the PSU's PCB power-take-offs... so only a few inches of 16awg for voltage drop (into the GPU), which reduces the amperage required (but is also unnecessary overkill).
It's the difference between NEMA 5-15 and 5-20: https://en.wikipedia.org/wiki/NEMA_connector#NEMA_5
... do you not have electric kettles in the US? Foolishly, I thought this was a standard kitchen appliance all over the world, I've even seen it in smaller cities in Peru.
My solution to drinking a cup of tea is also unusual: I have a no-longer-in-production Sunbeam Hotshot and I use it heat only as much water as I need right now.
It raises one tea-cup worth of water from whatever temperature it is that comes out of the cold tap to boiling in about 40 seconds.
I just dump a cup of water in, push one button to heat it up, wait until it boils, and then push another button to dispense that hot liquid into the cup that I'm using for tea.
It then turns itself off until next time.
We could even use 240v electric tea kettles here in the US if we wanted to; most kitchens with an electric range and oven have 240v (or 208v) outlets to plug them in to. But those outlets are usually inconveniently located for counter–top appliances. It wouldn’t cost much to add another above the counter, but it is rarely done in practice. Of course, in many parts of the US natural gas heating is cheaper than electric so the houses there are built for gas ranges and ovens instead.
(Note, my building is actually 3 phase 208 volt not 240volt so I don't have 240 volt plugs but 208volt plugs)
But really, doing a subpanel yourself to expand breaker capacity is a really simple project - most people if so inclined could do it themselves. Anywhere from $100-200 for the panel itself depending on how many spaces you feel like adding, up to $80 for a large enough breaker to feed it, and some tens of dollars for SER cable.
Otherwise, running your microwave, toaster, and coffee maker at the same time would likely trip the breaker.
And obviously, the stove/oven is on its own circuit unless it's gas.